VESTA-364N

PWB-1-BUS

Auxiliary Power Supply Module

Simple guide:

Introduction

The PWB-1-BUS is an auxiliary power supply module designed for integration into the BUS system, providing a maximum of 13.5V, 3A power supply to connected BUS devices.

When connected to the Hybrid Panel, the PWB-1-BUS module is supervised by and communicates to the Panel all the status changes, including AC power status, battery level, tamper status, and energy consumption data. Moreover, the PWB-1-BUS features voltage detection of the Hybrid Panel BUS VDD terminal. Only when the Hybrid Panel operates normally with power supplied at the BUS output will PWB-1-BUS supply power to connected BUS devices.

Identifying the Parts

  1. BUS Connection Terminals to the Hybrid Panel (4 wire: V, G, A, B)

  2. BUS Connection Terminals to powered BUS device (4 wire: V, G, A, B)

  3. BUS Connection Terminals to powered BUS device (4 wire: V, G, A, B)

  4. Battery Switch

Slide the battery switch to ON position, so that the backup battery will be charged when the AC power is connected and serve as a backup power source when AC power is missing.

  1. Battery Terminal

For the backup battery (One 12V 7.0Ah or 12V 17.2Ah Sealed Lead-acid battery)

  1. Terminal Resistor Jumper Switch (J3)

When the power supply module is connected in the BUS line as the furthest BUS device from the Hybrid Panel, please set both the Terminal Resistor Jumpers of the power supply module and the Hybrid Panel to ON. The BUS line’s communication ability will be enhanced

  • The Terminal Resistor Jumper of PWB-1-BUS is usually used when the power supply module is first connected to the Hybrid Panel without any powered BUS devices connected.

  • You can set he power supply module’s Terminal Resistor Jumper and the Hybrid Panel’s Terminal Resistor Jumper to ON to test if PWB-1-BUS can communicate well with the Panel.

  • If communication with the Panel is tested OK, you can start connecting the PWB-1-BUS to the powered devices. Then please set the power supply module’s Terminal Resistor Jumper to off, and set the Terminal Resistor Jumper of the farthest device in the BUS line to ON instead.

If the jumper is OFF (the jumper link is removed or “parked” on one pin), the communication ability is in normal level.

If the jumper is ON (the jumper link rests on both pins), the communication ability is enhanced.

  1. Mounting Holes

  2. AC Power Terminal and Power Cable

For 20Vac 50Hz/60Hz, 4A (80VA) power supply

  1. LED Indicator

  2. Test Button

Press to send a test signal to the Panel

  1. Tamper Switch Terminal Block 1

For connecting to the door tamper switch on the enclosure

  1. Tamper Switch Terminal Block 2 (optional)

For connecting to the wall-mount tamper switch on the enclosure

This terminal block is in a short status, connected with a black wire provided by factory before shipment.

If the enclosure is to be mounted on the wall and you wish to enable the wall tamper protection, please remove the black wire and connect this terminal block to the wall-mount tamper switch.

Accessories

  1. Standoff *4

  2. Standoff Nut *4

  3. 12V 7.0Ah Battery cable *2 (+, -)

Power Supply

Power Source:

  • The PWB-1-BUS is connected to 20Vac 50Hz/60Hz, 4A (80VA) power supply.

  • When power supply is interrupted and then restore, PWB-1-BUS will transmit an AC failure and an AC restore signal respectively.

Rechargeable Battery:

  • A 12V 7.0Ah or 12V 17.2Ah Sealed Lead-acid battery can be connected to serve as a backup in case of a power failure.

Power Output:

  • PWB-1-BUS can supply a maximum of 13.5V, 3A power to the connected BUS devices.

  • Through connection to the Hybrid Panel's BUS VDD terminal, PWB-1-BUS can detect if the Panel operates normally with power supplied at the BUS output. Only when PWB-1-BUS is properly connected to the Panel and confirms the Panel’s normal operation will PWB-1-BUS supply power to connected BUS devices.

Tamper Protection

Two Tamper Switch Terminals are provided: one for the door tamper switch and the other for the wall-mount tamper switch on the enclosure.

The Tamper Switches for door and wall-mount are in a normal position when the door is closed and the enclosure is securely mounted on the wall. Tamper violation happens when the door is opened or the enclosure is detached from the wall, causing the Tamper Switch to activate (Tamper Opened). A tamper open/close alert will be reported to the Control Panel.

Connecting to Panel and BUS Devices

  • To assist with cable connections, the terminal blocks on each BUS system module are color-coded.

  • When connecting the PWB-1-BUS to the Hybrid Panel, connect the four terminals (VDD, GND, 485A, 485B). Please refer to the picture below. Connecting the Red V terminal on PWB-1-BUS to the Hybrid Panel VDD terminal will enable BUS output voltage detection of the Hybrid Panel.

  • When connecting the PWB-1-BUS to the devices that are powered by the power supply module, please connect 4 terminals (VDD, GND, 485A, 485B).

Please refer to the BUS device connection examples (VST-892-BUS & DC-23-BUS) below.

Getting Started

After connecting the auxiliary power supply module to the Hybrid Panel (Please refer to Connecting to Panel and BUS devices section for details), please proceed to learning.

Learning

Step 1. After the PWB-1-BUS is connected to the Hybrid Panel, power on the Panel.

Step 2. On the Control Panel’s webpage, click “Learning” to enter learn page.

Step 3. Click “Start” to enter learning mode.

Step 4. Click “Add” to include the auxiliary power supply module into panel.

Step 5. If the auxiliary power supply module is successfully learnt into the system, the added device will be displayed in the “Learned Device” section. The Device Type will be shown as “PWB”.

Identification

The “Identify” function is used to localize a specific BUS device in the BUS wired system. This function is helpful in distinguishing which device is which especially in a large installation where numerous BUS devices are included.

To locate PWB-1-BUS in the BUS system:

Step 1. On Hybrid Panel’s webpage, click “Identify” under the device list after PWB’s device column entry.

Step 2. If PWB-1-BUS receives the signal from the Hybrid Panel, the webpage will display a success message and PWB-1-BUS’ LED indicator will flash 10 times to indicate where it is to the user.

Walk Test

To make sure the auxiliary power supply module is able to communicate with the Panel after it is learned-in, place the Control Panel in Walk Test mode and press the Test button on PWB-1-BUS to transmit a test signal to the Control Panel.

When the Panel receives the test signal, it will beep once and display PWB-1-BUS information accordingly on the top of the device list.

Supervisory Signal

After being learnt into the Control Panel, the auxiliary power supply module will automatically transmit Supervisory Signals every 75 seconds.

Energy Consumption Monitor

After being learnt into the Control Panel, the auxiliary power supply module will automatically transmit power consumption data, including battery level, BUS voltage, and BUS current to the Control Panel every 30-50 minutes.

  • When the battery level is below or equal to 20%, a low battery signal will be sent to the Panel.

  • When battery level is 0%, it indicates one of the follow situations: battery disconnection, battery switch in off position, or battery failure.

Users can also manually query the power consumption data on Device Edit page.

Mounting the PWB-1-BUS in the enclosure (AWO978)

Step 1. Locate the locations for standoffs on the enclosure AWO978 (①– A, B, C, D), and the mounting holes on the PWB-1-BUS (② – A, B, C, D).

Step 2. Use the provided standoffs and nuts to firmly fix PWB-1-BUS in place.

Step 3. Connect the tamper switch terminal block 1 to the door tamper switch on the enclosure.

Step 4. (Optional) Connect the terminal block 2 to the wall-mount tamper switch on the enclosure.

Tamper Switch Terminal Block 2 is in a short status, connected with a black wire provided by factory before shipment. If the enclosure is to be mounted on the wall and you wish to enable the wall tamper protection, please remove the black wire and connect Tamper Switch Terminal Block 2 to the wall-mount tamper switch.

Step 5. Install the backup battery. Follow the steps below:

  1. Connect the GND cable (Black) to the negative pole (-) of battery.

  2. Connect the power cable (Red) to the positive pole (+) of battery

  3. Fix the backup battery to the enclosure.

Battery options: 12V 7.0Ah or 12V 17.2Ah Sealed Lead-acid battery.

Step 6. Connect the AC power cable to the 20Vac 50Hz/60Hz, 4A (80VA) power supply.

Step 7. Slide the battery switch to ON. The installation is now completed.