VMAX BUS TIPS

V-MAX BUS SYSTEM in VESTA panels tips:

GENERAL RULES:

  • From one device or bus start to the next, no more than 300 metres may be exceeded.

  • Take into account the current required for the system (use calculator or consumption table of the devices).

  • Take into account the voltage drop (calculator) If there is a voltage drop, a power supply or isolator-amplifier can be used

  • The limit of the BUS system at distance level will depend on the consumption and voltage at each point, if a sufficient current and voltage is guaranteed at each device, the system will operate correctly.

CASE 1: ONE LINE OF BUS

CASE 2: TWO LINES OF BUS (STAR)

CASE 3: TREE LINES

CASE 3A. WITH ISOLATOR (Recomended for this CASE)

CASE 3B. WITH NO ISOLATOR (TIP: Place resistors in the longest BUS sections.)

CASE 4: FOUR LINES OF BUS

CONSUMPTION TABLE OF V-MAX BUS DEVICES

DEVICE

Current Consumption (mA)

Current Consumption (A)

Voltage

892-EX-BUS

130

0,1300

4,50

KPT-35-BUS

171

0,1710

4,50

BX-32-BUS

364,9

0,3649

4,50

892-BUS

229,8

0,2298

4,50

892-EX-BUS

397,7

0,3977

4,50

DC-23-BUS

30,6

0,0306

4,50

DCSV-29-BUS

13,2

0,0132

4,50

IR-35-BUS

41,4

0,0414

4,50

SR-35-BUS

64,4

0,0644

4,50

AMP-BUS

3,58

0,0036

4,50

WEZ

31

0,0310

4,50

WEZC-8

95

0,0950

4,50

WEP

240

0,2400

6,50

TSP-BUS

1038

1,0380

6,00

WGT-1-COMBO-F1

354,6

0,3546

8,00

KP-35-COMBO

82,7

0,0827

4,50