> For the complete documentation index, see [llms.txt](https://vesta-guide.gitbook.io/vesta-guide/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://vesta-guide.gitbook.io/vesta-guide/tips-and-help/vmax-bus-tips.md).

# VMAX BUS TIPS

**V-MAX BUS SYSTEM in VESTA panels tips:**

## **GENERAL RULES:**

* From one device or bus start to the next, no more than 300 metres may be exceeded.
* Take into account the current required for the system (use calculator or consumption table of the devices).
* Take into account the voltage drop (calculator) If there is a voltage drop, a power supply or isolator-amplifier can be used
* The limit of the BUS system at distance level will depend on the consumption and voltage at each point, if a sufficient current and voltage is guaranteed at each device, the system will operate correctly.

![](/files/Eu95eKgqGWUict3gbH1h)

## **CASE 1: ONE LINE OF BUS**

![](/files/kkVeEz99RoEtLzlDejLt)

## **CASE 2: TWO LINES OF BUS (STAR)**

![](/files/IiXEpDkrUFFPsj6H0d3V)

## **CASE 3: TREE LINES**

### **CASE 3A. WITH ISOLATOR (Recomended for this CASE)**

![](/files/xzyTJfxujz2VZEZTdByI)

### **CASE 3B. WITH NO ISOLATOR (TIP: Place resistors in the longest BUS sections.)**

![](/files/Y7fBn7841d8rgkQwwu1k)

## **CASE 4: FOUR LINES OF BUS**

![](/files/HiPmCKoQ9PCeikfyAeGz)

## CONSUMPTION TABLE OF V-MAX BUS DEVICES

<table data-header-hidden data-full-width="false"><thead><tr><th></th><th></th><th></th><th></th></tr></thead><tbody><tr><td>DEVICE</td><td>Current Consumption (mA)</td><td>Current Consumption (A)</td><td>Voltage</td></tr><tr><td>892-EX-BUS</td><td>130</td><td>0,1300</td><td>4,50</td></tr><tr><td>KPT-35-BUS</td><td>171</td><td>0,1710</td><td>4,50</td></tr><tr><td>BX-32-BUS</td><td>364,9</td><td>0,3649</td><td>4,50</td></tr><tr><td>892-BUS</td><td>229,8</td><td>0,2298</td><td>4,50</td></tr><tr><td>892-EX-BUS</td><td>397,7</td><td>0,3977</td><td>4,50</td></tr><tr><td>DC-23-BUS</td><td>30,6</td><td>0,0306</td><td>4,50</td></tr><tr><td>DCSV-29-BUS</td><td>13,2</td><td>0,0132</td><td>4,50</td></tr><tr><td>IR-35-BUS</td><td>41,4</td><td>0,0414</td><td>4,50</td></tr><tr><td>SR-35-BUS</td><td>64,4</td><td>0,0644</td><td>4,50</td></tr><tr><td>AMP-BUS</td><td>3,58</td><td>0,0036</td><td>4,50</td></tr><tr><td>WEZ</td><td>31</td><td>0,0310</td><td>4,50</td></tr><tr><td>WEZC-8</td><td>95</td><td>0,0950</td><td>4,50</td></tr><tr><td>WEP</td><td>240</td><td>0,2400</td><td>6,50</td></tr><tr><td>TSP-BUS</td><td>1038</td><td>1,0380</td><td>6,00</td></tr><tr><td>WGT-1-COMBO-F1</td><td>354,6</td><td>0,3546</td><td>8,00</td></tr><tr><td>KP-35-COMBO</td><td>82,7</td><td>0,0827</td><td>4,50</td></tr></tbody></table>

## **Vesta V-MAX Bus - Recommended Cable Type**

The Vesta V-MAX BUS uses RS485 communication. Cable choice matters for reliable operation.

#### **Recommended: Twisted Pair + Shielded**

Use a twisted pair cable with shielding. Twisted pair is optimal for RS485 bus communication as it reduces interference and ensures stable data transmission over long runs.

#### **Alternative: 4+2 Shielded alarm cable**

If twisted pair is not available, a standard **4+2** shielded alarm cable can be used:

* Use the **0.75mm² or thicker** conductors for power (2 wires)
* Use the remaining wires for the RS485 data signals (A/B)

{% hint style="info" %}
**Maximum distance:** 100 meters. Do not exceed this when using 4+2 cable.
{% endhint %}

#### **Summary**

| Cable Type                                  | Max Distance from 1 device to other | Notes                                      |
| ------------------------------------------- | ----------------------------------- | ------------------------------------------ |
| Twisted Pair + Shielded                     | 300m                                | Best option. Always recommended.           |
| 4+2 Shielded alarm cable (0.75mm²+ 0.25mm²) | 100m                                | Use only if twisted pair is not available. |

In installations close to the distance limit, measure the voltage at the last BUS device while the system is operating. If the voltage is unstable or below the required value, shorten the BUS run or add an isolator-amplifier or auxiliary power supply. This prevents intermittent faults, missed events, and BUS communication loss.


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation dynamically by asking a question.

Perform an HTTP GET request on the current page URL with the `ask` query parameter, and the optional `goal` query parameter:

```
GET https://vesta-guide.gitbook.io/vesta-guide/tips-and-help/vmax-bus-tips.md?ask=<question>&goal=<endgoal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is optional and describes the broader end goal you are ultimately trying to accomplish on behalf of the user. GitBook uses it to tailor the answer towards what is most useful for that goal.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.