VMAX BUS TIPS
V-MAX BUS SYSTEM in VESTA panels tips:
GENERAL RULES:
From one device or bus start to the next, no more than 300 metres may be exceeded.
Take into account the current required for the system (use calculator or consumption table of the devices).
Take into account the voltage drop (calculator) If there is a voltage drop, a power supply or isolator-amplifier can be used
The limit of the BUS system at distance level will depend on the consumption and voltage at each point, if a sufficient current and voltage is guaranteed at each device, the system will operate correctly.

CASE 1: ONE LINE OF BUS

CASE 2: TWO LINES OF BUS (STAR)

CASE 3: TREE LINES
CASE 3A. WITH ISOLATOR (Recomended for this CASE)

CASE 3B. WITH NO ISOLATOR (TIP: Place resistors in the longest BUS sections.)

CASE 4: FOUR LINES OF BUS

CONSUMPTION TABLE OF V-MAX BUS DEVICES
DEVICE
Current Consumption (mA)
Current Consumption (A)
Voltage
892-EX-BUS
130
0,1300
4,50
KPT-35-BUS
171
0,1710
4,50
BX-32-BUS
364,9
0,3649
4,50
892-BUS
229,8
0,2298
4,50
892-EX-BUS
397,7
0,3977
4,50
DC-23-BUS
30,6
0,0306
4,50
DCSV-29-BUS
13,2
0,0132
4,50
IR-35-BUS
41,4
0,0414
4,50
SR-35-BUS
64,4
0,0644
4,50
AMP-BUS
3,58
0,0036
4,50
WEZ
31
0,0310
4,50
WEZC-8
95
0,0950
4,50
WEP
240
0,2400
6,50
TSP-BUS
1038
1,0380
6,00
WGT-1-COMBO-F1
354,6
0,3546
8,00
KP-35-COMBO
82,7
0,0827
4,50