V-MAX BUS SYSTEM in VESTA panels tips:
GENERAL RULES:
From one device or bus start to the next, no more than 300 metres may be exceeded.
Take into account the current required for the system (use calculator or consumption table of the devices).
Take into account the voltage drop (calculator) If there is a voltage drop, a power supply or isolator-amplifier can be used
The limit of the BUS system at distance level will depend on the consumption and voltage at each point, if a sufficient current and voltage is guaranteed at each device, the system will operate correctly.
CASE 1: ONE LINE OF BUS
CASE 2: TWO LINES OF BUS (STAR)
CASE 3: TREE LINES
CASE 3A. WITH ISOLATOR (Recomended for this CASE)
CASE 3B. WITH NO ISOLATOR (TIP: Place resistors in the longest BUS sections.)
CASE 4: FOUR LINES OF BUS