> For the complete documentation index, see [llms.txt](https://vesta-guide.gitbook.io/vesta-guide/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://vesta-guide.gitbook.io/vesta-guide/vesta-156n.md).

# VESTA-156N

Configuration manual of the VESTA-156N

<figure><img src="/files/HxEGqgemq9WasdXarcxT" alt=""><figcaption></figcaption></figure>

## FIRST OF ALL:

### • Connect the battery of the I/O module

![](/files/26VFvDqqdjBFgjeKxic7)

{% hint style="danger" %}
NOTE:

### Connect the smoke generator in the terminals“smoke” only AFTER made the tests of working.

{% endhint %}

## Learning I/O module on the panel

1. Activate the learning function on the panel (for further info, refer to the panel manual)

![Add device](/files/PynucBxGC6nhq8hTFGnB)

![Select Others](/files/xPw2R5VCtjYubXW03LGO)

2. Press the button on the I/O module installed inside the VESTA-156

<figure><img src="/files/yVCM8zB3KWDXc4DhhDAc" alt=""><figcaption></figcaption></figure>

3. Select the detected device and press OK

![](/files/CadFwDRQjroKQjz5idyn)

4. Assign the appropriate area to the output device (DO), and choose the zone number and the name of the device: SMOKE ACTIVATION

![](/files/2VOJaFchhNVJPdFNToGB)

{% hint style="warning" %}
Note: The output module (DO) must be set as. "Separate devices"
{% endhint %}

5. Assign at the (DI) the same area to the output device (DO) and choose the zone number and the device name: SMOKE TAMPER.

![](/files/HQGL7ajESZJxT2wnSudj)

6. Set the input module as a 24H Burglar Alarm

## Configuration activation rule

In the menu "automation rule" create a new rule as indicated below:

![](/files/OuYyceWQj6PqlT8cBue8)

## Double coincidence configuration

In the device settings, set at least 2 devices with the "Cross zone" attribute to activate the smoke generator ONLY in the event of the activation of both devices in a programmable time and thus avoid improper activations.

Example of the Cross Zone programming:

![PIRCAM zone ](/files/1wpyvxWGqoJW3Eam4XqO)

![Magnetic Contac zone](/files/D9ZHXqG3BEg0wd7raCnD)

In the menu "Security“, set the timer for the cross zones to 1 minute or more (time within which the 2 zones must be activated to trigger the smoke generator)

![](/files/4LVO3uqyoPjc4OldLW0R)
